POWER CABLE (PVC INSULATED) COPPER / ALUMINIUM CONDUCTOR

Category:

1.1 kV PVC insulated armoured power cable with aluminium or copper conductor to IS 1554 (Part 1). Available in 1, 2, 3, 3.5 and 4 core, 4 sq. mm to 630 sq. mm. Cable codes AYFY / YFY, AYWY / YWY, AYFaY / AYWaY.

POWER CABLE (PVC INSULATED)
COPPER / ALUMINIUM CONDUCTOR

1.1 kV PVC insulated, PVC sheathed, armoured power cables with aluminium or copper conductor, made to IS 1554 (Part 1). Cable codes: A = aluminium conductor (no prefix = copper), Y = PVC, F = steel flat strip armour, W = steel round wire armour, Fa / Wa = aluminium strip / wire armour. Example: AYFY = aluminium conductor, PVC insulated, steel strip armoured, PVC sheathed.

  • Voltage grade: 1.1 kV (1100 V)
  • Standard: IS 1554 (Part 1)
  • Conductor: Aluminium / Copper, Class 2 of IS 8130
  • Insulation: PVC Type-A or HR PVC Type-C to IS 5831
  • Sheath: PVC ST-1 (ST-2, FR, FRLS on request)
  • Armour: Flat strip or round wire
  • Cores: 1, 2, 3, 3½ and 4
  • Sizes: 4 sq. mm to 630 sq. mm

TECHNICAL DETAILS – 1.1 kV SINGLE CORE, ALUMINIUM / COPPER CONDUCTOR,
PVC INSULATED, ARMOURED CABLE

Physical Parameters

Single Core PVC armoured power cable – physical parameters (IS 1554 Part 1). Cable codes: AYFaY / YFaY, AYWaY / YWaY
Size Min. No. of Strands in Conductor Nominal Insulation Thickness Flat Strip Armoured (AYFaY / YFaY) Round Wire Armoured (AYWaY / YWaY)
Aluminium Copper Armour Strip Dimension Min. Outer Sheath Thickness Approx. Overall Dia Approx. Weight – Al Conductor Approx. Weight – Cu Conductor Nominal Dia of Armour Wire Min. Outer Sheath Thickness Approx. Overall Dia Approx. Weight – Al Conductor Approx. Weight – Cu Conductor
sq. mm N N mm mm mm mm kg/km kg/km mm mm mm kg/km kg/km
4 1/3 1/3 1.30 N/A N/A N/A N/A N/A 1.40 1.24 11 130 160
6 1/3 1/3 1.30 N/A N/A N/A N/A N/A 1.40 1.24 12 150 190
10 1/7 6 1.30 N/A N/A N/A N/A N/A 1.40 1.24 13 170 240
16 6 6 1.30 N/A N/A N/A N/A N/A 1.40 1.24 13 250 300
25 6 6 1.50 N/A N/A N/A N/A N/A 1.40 1.24 15 300 450
35 6 6 1.50 N/A N/A N/A N/A N/A 1.40 1.24 16 350 550
50 6 6 1.70 N/A N/A N/A N/A N/A 1.40 1.24 17 400 700
70 12 12 1.70 N/A N/A N/A N/A N/A 1.60 1.40 19 500 900
95 15 15 1.90 4×0.80 1.40 20 600 1150 1.60 1.40 22 700 1250
120 15 18 1.90 4×0.80 1.40 22 700 1400 1.60 1.40 23 800 1450
150 15 18 2.10 4×0.80 1.40 23 800 1700 1.60 1.40 25 900 1750
185 30 30 2.30 4×0.80 1.40 25 1000 2050 1.60 1.40 27 1050 2150
240 30 34 2.50 4×0.80 1.40 28 1200 2600 1.60 1.56 30 1350 2750
300 30 34 2.70 4×0.80 1.56 31 1500 3250 1.60 1.56 33 1600 3350
400 53 53 3.00 4×0.80 1.56 35 1850 4100 2.00 1.56 38 2050 4300
500 53 53 3.40 4×0.80 1.56 39 2300 5150 2.00 1.72 42 2550 5400
630 53 53 3.90 4×0.80 1.72 44 2900 6650 2.00 1.88 46 3200 6950

Electrical Parameters

Single Core PVC armoured power cable – electrical parameters
Size Max. Conductor DC Resistance at 20°C Approx. Conductor AC Resistance at 70°C Reactance at 50 Hz (Approx.) Capacitance (Approx.) Current Rating – Aluminium Conductor Current Rating – Copper Conductor Short Circuit Rating for 1 s
Aluminium Copper Aluminium Copper Ground Duct Air Ground Duct Air Aluminium Copper
sq. mm Ω/km Ω/km Ω/km Ω/km Ω/km µF/km A A A A A A kA kA
4 7.41 4.61 8.89 5.53 0.157 0.48 36 33 32 46 42 43 0.304 0.460
6 4.61 3.08 5.53 3.70 0.148 0.56 44 42 41 57 54 54 0.456 0.690
10 3.08 1.83 3.70 2.20 0.138 0.67 59 56 56 75 72 72 0.760 1.15
16 1.91 1.15 2.29 1.38 0.128 0.81 75 71 72 94 92 92 1.22 1.84
25 1.20 0.727 1.44 0.87 0.120 0.87 97 93 99 125 120 125 1.90 2.88
35 0.868 0.524 1.04 0.63 0.114 1.00 120 110 120 150 140 155 2.66 4.03
50 0.641 0.387 0.769 0.464 0.110 1.03 145 130 150 180 165 190 3.80 5.75
70 0.443 0.268 0.532 0.322 0.103 1.21 170 155 185 220 200 235 5.32 8.05
95 0.320 0.193 0.384 0.232 0.101 1.27 205 180 215 265 230 275 7.22 10.90
120 0.253 0.153 0.304 0.184 0.096 1.42 230 200 240 300 255 310 9.12 13.80
150 0.206 0.1240 0.247 0.1488 0.094 1.42 265 220 270 340 280 345 11.40 17.30
185 0.164 0.0991 0.197 0.1189 0.092 1.44 300 240 305 380 305 390 14.10 21.30
240 0.125 0.0754 0.151 0.0912 0.090 1.53 335 270 350 420 340 445 18.20 27.60
300 0.100 0.0601 0.122 0.0733 0.088 1.56 370 295 395 465 370 500 22.80 34.50
400 0.0778 0.0470 0.0961 0.0580 0.088 1.59 410 335 455 500 405 570 30.40 46.00
500 0.0605 0.0366 0.076 0.0459 0.087 1.67 435 355 490 540 430 610 38.00 57.50
630 0.0469 0.0283 0.0610 0.0368 0.086 1.67 485 395 560 590 465 680 47.88 72.50

Cross-Sectional View

Cross-section of 1.1 kV single core PVC insulated armoured power cable

  1. Conductor: Aluminium / Copper as per Class 2 of IS 8130. Aluminium: 4, 6 and 10 sq. mm solid / stranded non-compacted circular; 16 sq. mm and above stranded compacted circular. Copper: 4 and 6 sq. mm solid / stranded non-compacted circular; 10 sq. mm and above stranded compacted circular.
  2. Insulation: PVC Type-A / HR PVC Type-C as per IS 5831; colour: black.
  3. Inner Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS.
  4. Armouring: Single layer of aluminium round wire / flat strip.
  5. Outer Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS. Colour: black or any other colour as per requirement.

TECHNICAL DETAILS – 1.1 kV TWO CORE, ALUMINIUM / COPPER CONDUCTOR,
PVC INSULATED, ARMOURED CABLE

Physical Parameters

Two Core PVC armoured power cable – physical parameters (IS 1554 Part 1). Cable codes: AYFY / YFY, AYWY / YWY
Size Min. No. of Strands in Conductor Nominal Insulation Thickness Min. Inner Sheath Thickness Flat Strip Armoured (AYFY / YFY) Round Wire Armoured (AYWY / YWY)
Aluminium Copper Armour Strip Dimension Min. Outer Sheath Thickness Approx. Overall Dia Approx. Weight – Al Conductor Approx. Weight – Cu Conductor Nominal Dia of Armour Wire Min. Outer Sheath Thickness Approx. Overall Dia Approx. Weight – Al Conductor Approx. Weight – Cu Conductor
sq. mm N N mm mm mm mm mm kg/km kg/km mm mm mm kg/km kg/km
4 1/3 1/3 1.00 0.30 N/A N/A N/A N/A N/A 1.40 1.24 15 460 520
6 1/3 1/3 1.00 0.30 N/A N/A N/A N/A N/A 1.40 1.24 16 530 620
10 1/7 6 1.00 0.30 N/A N/A N/A N/A N/A 1.40 1.24 18 620 780
16 6 6 1.00 0.30 4×0.80 1.40 17 500 700 1.40 1.40 18 700 850
25 6 6 1.20 0.30 4×0.80 1.40 19 600 950 1.60 1.40 21 850 1150
35 6 6 1.20 0.30 4×0.80 1.40 21 750 1150 1.60 1.40 22 950 1350
50 6 6 1.40 0.30 4×0.80 1.40 23 900 1450 1.60 1.56 25 1200 1750
70 12 12 1.40 0.30 4×0.80 1.56 26 1100 1900 1.60 1.56 27 1400 2200
95 15 15 1.60 0.40 4×0.80 1.56 29 1400 2500 2.00 1.56 32 1900 3000
120 15 18 1.60 0.40 4×0.80 1.56 31 1600 3000 2.00 1.72 34 2150 3550
150 15 18 1.80 0.40 4×0.80 1.72 34 1900 3650 2.00 1.72 36 2500 4200
185 30 30 2.00 0.50 4×0.80 1.88 37 2300 4450 2.00 1.88 40 2950 5100
240 30 34 2.20 0.50 6.10×1.40 2.04 42 2850 5700 2.50 2.04 46 3850 6700
300 30 34 2.40 0.60 6.10×1.40 2.20 46 3400 6950 2.50 2.20 49 4550 8100
400 53 53 2.60 0.70 6.10×1.40 2.36 51 4200 8750 3.15 2.52 56 6050 10600
500 53 53 3.00 0.70 6.10×1.40 2.68 57 5250 11050 3.15 2.84 62 7350 13150
630 53 53 3.40 0.70 6.10×1.40 2.84 64 6550 14050 4.00 3.00 70 9750 17250

Electrical Parameters

Two Core PVC armoured power cable – electrical parameters
Size Max. Conductor DC Resistance at 20°C Approx. Conductor AC Resistance at 70°C Reactance at 50 Hz (Approx.) Capacitance (Approx.) Current Rating – Aluminium Conductor Current Rating – Copper Conductor Short Circuit Rating for 1 s
Aluminium Copper Aluminium Copper Ground Duct Air Ground Duct Air Aluminium Copper
sq. mm Ω/km Ω/km Ω/km Ω/km Ω/km µF/km A A A A A A kA kA
4 7.41 4.61 8.89 5.53 0.157 0.48 36 33 32 46 42 43 0.304 0.460
6 4.61 3.08 5.53 3.70 0.148 0.56 44 42 41 57 54 54 0.456 0.690
10 3.08 1.83 3.70 2.20 0.138 0.67 59 56 56 75 72 72 0.760 1.15
16 1.91 1.15 2.29 1.38 0.128 0.81 75 71 72 94 92 92 1.22 1.84
25 1.20 0.727 1.44 0.87 0.120 0.87 97 93 99 125 120 125 1.90 2.88
35 0.868 0.524 1.04 0.63 0.114 1.00 120 110 120 150 140 155 2.66 4.03
50 0.641 0.387 0.769 0.464 0.110 1.03 145 130 150 180 165 190 3.80 5.75
70 0.443 0.268 0.532 0.322 0.103 1.21 170 155 185 220 200 235 5.32 8.05
95 0.320 0.193 0.384 0.232 0.101 1.27 205 180 215 265 230 275 7.22 10.90
120 0.253 0.153 0.304 0.184 0.096 1.42 230 200 240 300 255 310 9.12 13.80
150 0.206 0.1240 0.247 0.1488 0.094 1.42 265 220 270 340 280 345 11.40 17.30
185 0.164 0.0991 0.197 0.1189 0.092 1.44 300 240 305 380 305 390 14.10 21.30
240 0.125 0.0754 0.151 0.0912 0.090 1.53 335 270 350 420 340 445 18.20 27.60
300 0.100 0.0601 0.122 0.0733 0.088 1.56 370 295 395 465 370 500 22.80 34.50
400 0.0778 0.0470 0.0961 0.0580 0.088 1.59 410 335 455 500 405 570 30.40 46.00
500 0.0605 0.0366 0.076 0.0459 0.087 1.67 435 355 490 540 430 610 38.00 57.50
630 0.0469 0.0283 0.0610 0.0368 0.086 1.67 485 395 560 590 465 680 47.88 72.50

Cross-Sectional View

Cross-section of 1.1 kV two core PVC insulated armoured power cable

  1. Conductor: Aluminium / Copper as per Class 2 of IS 8130. Aluminium: 4, 6 and 10 sq. mm solid / stranded non-compacted circular; 16 sq. mm and above stranded compacted shaped. Copper: 4 and 6 sq. mm solid / stranded non-compacted circular; 10 sq. mm stranded compacted circular; 16 sq. mm and above stranded compacted shaped.
  2. Insulation: PVC Type-A / HR PVC Type-C as per IS 5831; colours: red and black.
  3. Inner Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS.
  4. Outer Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS. Colour: black or any other colour as per requirement.

Armouring: Single layer of galvanized steel round wire / flat strip.

TECHNICAL DETAILS – 1.1 kV THREE CORE, ALUMINIUM / COPPER CONDUCTOR,
PVC INSULATED, ARMOURED CABLE

Physical Parameters

Three Core PVC armoured power cable – physical parameters (IS 1554 Part 1). Cable codes: AYFY / YFY, AYWY / YWY
Size Min. No. of Strands in Conductor Nominal Insulation Thickness Min. Inner Sheath Thickness Flat Strip Armoured (AYFY / YFY) Round Wire Armoured (AYWY / YWY)
Aluminium Copper Armour Strip Dimension Min. Outer Sheath Thickness Approx. Overall Dia Approx. Weight – Al Conductor Approx. Weight – Cu Conductor Nominal Dia of Armour Wire Min. Outer Sheath Thickness Approx. Overall Dia Approx. Weight – Al Conductor Approx. Weight – Cu Conductor
sq. mm N N mm mm mm mm mm kg/km kg/km mm mm mm kg/km kg/km
4 1/3 1/3 1.00 0.30 N/A N/A N/A N/A N/A 1.40 1.24 16 460 540
6 1/3 1/3 1.00 0.30 N/A N/A N/A N/A N/A 1.40 1.24 17 530 650
10 1/7 6 1.00 0.30 N/A N/A N/A N/A N/A 1.40 1.24 19 620 840
16 6 6 1.00 0.30 4×0.80 1.40 19 600 950 1.60 1.40 21 850 1100
25 6 6 1.20 0.30 4×0.80 1.40 22 800 1250 1.60 1.40 23 1050 1500
35 6 6 1.20 0.30 4×0.80 1.40 23 950 1550 1.60 1.40 25 1200 1800
50 6 6 1.40 0.30 4×0.80 1.40 27 1200 2050 1.60 1.56 28 1500 2300
70 12 12 1.40 0.30 4×0.80 1.56 30 1500 2700 1.60 1.56 32 2000 3200
95 15 15 1.60 0.40 4×0.80 1.56 33 1850 3550 2.00 1.72 36 2450 4150
120 15 18 1.60 0.40 4×0.80 1.56 36 2200 4300 2.00 1.72 39 2800 4900
150 15 18 1.80 0.40 4×0.80 1.72 40 2650 5250 2.00 1.88 43 3350 5900
185 30 30 2.00 0.50 4×0.80 1.88 44 3150 6400 2.00 2.04 48 4300 7500
240 30 34 2.20 0.50 6.10×1.60 1.88 50 4000 8250 2.50 2.20 53 5250 9450
300 30 34 2.40 0.60 6.10×1.60 2.20 55 4800 10150 2.50 2.36 58 6150 11450
400 53 53 2.60 0.70 6.10×1.60 2.36 61 5950 12750 3.15 2.68 66 8200 14950
500 53 53 3.00 0.70 6.10×1.60 2.52 69 7450 16200 3.15 3.00 74 10000 18700
630 53 53 3.40 0.70 6.10×1.60 2.84 77 9300 20600 4.00 3.00 84 13150 24400

Electrical Parameters

Three Core PVC armoured power cable – electrical parameters
Size Max. Conductor DC Resistance at 20°C Approx. Conductor AC Resistance at 70°C Reactance at 50 Hz (Approx.) Capacitance (Approx.) Current Rating – Aluminium Conductor Current Rating – Copper Conductor Short Circuit Rating for 1 s
Aluminium Copper Aluminium Copper Ground Duct Air Ground Duct Air Aluminium Copper
sq. mm Ω/km Ω/km Ω/km Ω/km Ω/km µF/km A A A A A A kA kA
4 7.41 4.61 8.89 5.53 0.098 0.23 28 23 23 36 30 30 0.304 0.460
6 4.61 3.08 5.53 3.70 0.096 0.28 35 30 30 45 38 39 0.456 0.690
10 3.08 1.83 3.70 2.20 0.091 0.34 46 39 40 60 50 52 0.760 1.15
16 1.91 1.15 2.29 1.38 0.085 0.40 60 50 51 77 64 66 1.22 1.84
25 1.20 0.727 1.44 0.87 0.083 0.42 76 63 70 99 81 90 1.90 2.88
35 0.868 0.524 1.04 0.63 0.082 0.48 92 77 86 120 99 110 2.66 4.03
50 0.641 0.387 0.769 0.464 0.082 0.49 110 95 105 145 125 135 3.80 5.75
70 0.443 0.268 0.532 0.322 0.076 0.56 135 115 130 175 150 165 5.32 8.05
95 0.320 0.193 0.384 0.232 0.076 0.58 165 140 155 210 175 200 7.22 10.90
120 0.253 0.153 0.304 0.184 0.075 0.63 185 155 180 240 195 230 9.12 13.80
150 0.206 0.1240 0.247 0.1488 0.074 0.63 210 175 205 270 225 265 11.40 17.30
185 0.164 0.0991 0.197 0.1189 0.074 0.64 235 200 240 300 255 308 14.10 21.30
240 0.125 0.0754 0.151 0.0912 0.073 0.67 275 235 280 345 295 355 18.20 27.60
300 0.100 0.0601 0.122 0.0733 0.073 0.68 305 260 315 385 335 400 22.80 34.50
400 0.0778 0.0470 0.0961 0.0580 0.072 0.70 335 290 375 425 360 455 30.40 46.00
500 0.0605 0.0366 0.076 0.0459 0.072 0.70 370 320 425 470 390 520 38.00 57.50
630 0.0469 0.0283 0.0610 0.0368 0.072 0.70 405 350 480 555 470 675 47.90 72.50

Cross-Sectional View

Cross-section of 1.1 kV three core PVC insulated armoured power cable

  1. Conductor: Aluminium / Copper as per Class 2 of IS 8130. Aluminium: 4, 6 and 10 sq. mm solid / stranded non-compacted circular; 16 sq. mm and above stranded compacted shaped. Copper: 4 and 6 sq. mm solid / stranded non-compacted circular; 10 sq. mm stranded compacted circular; 16 sq. mm and above stranded compacted shaped.
  2. Insulation: PVC Type-A / HR PVC Type-C as per IS 5831; colours: red, yellow and blue.
  3. Inner Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS.
  4. Armouring: Single layer of galvanized steel round wire / flat strip.
  5. Outer Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS. Colour: black or any other colour as per requirement.

TECHNICAL DETAILS – 1.1 kV THREE & HALF CORE, ALUMINIUM / COPPER CONDUCTOR,
PVC INSULATED, ARMOURED CABLE

Physical Parameters

Three & Half Core PVC armoured power cable – physical parameters (IS 1554 Part 1). Cable codes: AYFY / YFY, AYWY / YWY
Size (Phase + Neutral) Min. No. of Strands in Conductor Nominal Insulation Thickness Min. Inner Sheath Thickness Flat Strip Armoured (AYFY / YFY) Round Wire Armoured (AYWY / YWY)
Aluminium Copper Armour Strip Dimension Min. Outer Sheath Thickness Approx. Overall Dia Approx. Weight – Al Conductor Approx. Weight – Cu Conductor Nominal Dia of Armour Wire Min. Outer Sheath Thickness Approx. Overall Dia Approx. Weight – Al Conductor Approx. Weight – Cu Conductor
sq. mm N N mm mm mm mm mm kg/km kg/km mm mm mm kg/km kg/km
3×25+16 6/6 6/6 1.20/1.00 0.30 4×0.80 1.40 23 900 1450 1.60 1.40 25 1150 1700
3×35+16 6/6 6/6 1.20/1.00 0.30 4×0.80 1.40 25 1050 1800 1.60 1.40 27 1350 2050
3×50+25 6/6 6/6 1.40/1.20 0.30 4×0.80 1.56 29 1350 2350 2.00 1.56 30 1650 2600
3×70+35 12/6 12/6 1.40/1.20 0.40 4×0.80 1.56 32 1700 3100 2.00 1.56 34 2200 3600
3×95+50 15/6 15/6 1.60/1.40 0.40 4×0.80 1.56 36 2150 4050 2.00 1.72 39 2800 4750
3×120+70 15/12 18/12 1.60/1.40 0.50 4×0.80 1.72 40 2550 5050 2.00 1.88 42 3300 5750
3×150+70 15/12 18/12 1.80/1.40 0.50 4×0.80 1.88 44 3000 6000 2.00 1.88 46 3750 6700
3×185+95 30/15 30/15 2.00/1.60 0.50 4×0.80 2.04 48 3650 7400 2.50 2.04 51 4850 8650
3×240+120 30/15 34/18 2.20/1.60 0.60 6.10×1.40 2.20 53 4500 9400 2.50 2.36 57 5850 10800
3×300+150 30/15 34/18 2.40/1.80 0.60 6.10×1.40 2.36 58 5450 11650 3.15 2.52 63 7600 13800
3×400+185 53/30 53/30 2.60/2.00 0.70 6.10×1.40 2.68 64 6750 14600 3.15 2.68 69 9000 16850
3×500+240 53/30 53/34 3.00/2.20 0.70 6.10×1.40 2.84 76 8550 18700 4.00 3.00 83 12400 22500
3×630+300 53/30 53/34 3.40/2.40 0.70 6.10×1.40 3.00 84 10600 23700 4.00 3.00 91 14750 27800

Electrical Parameters

Three & Half Core PVC armoured power cable – electrical parameters
Size (Phase + Neutral) Max. Conductor DC Resistance at 20°C Approx. Conductor AC Resistance at 70°C Reactance at 50 Hz (Approx.) Capacitance (Approx.) Current Rating – Aluminium Conductor Current Rating – Copper Conductor Short Circuit Rating for 1 s
Aluminium Copper Aluminium Copper Ground Duct Air Ground Duct Air Aluminium Copper
sq. mm Ω/km Ω/km Ω/km Ω/km Ω/km µF/km A A A A A A kA kA
3×25+16 1.20 0.727 1.44 0.87 0.083 0.42 76 63 70 99 81 90 1.90 2.88
3×35+16 0.868 0.524 1.04 0.63 0.082 0.48 92 77 86 120 99 110 2.66 4.03
3×50+25 0.641 0.387 0.769 0.464 0.082 0.49 110 95 105 145 125 135 3.80 5.75
3×70+35 0.443 0.268 0.532 0.322 0.076 0.56 135 115 130 175 150 165 5.32 8.05
3×95+50 0.320 0.193 0.384 0.232 0.076 0.58 165 140 155 210 175 200 7.22 10.90
3×120+70 0.253 0.153 0.304 0.184 0.075 0.63 185 155 180 240 195 230 9.12 13.80
3×150+70 0.206 0.1240 0.247 0.1488 0.074 0.63 210 175 205 270 225 265 11.40 17.30
3×185+95 0.164 0.0991 0.197 0.1189 0.074 0.64 235 200 240 300 255 305 14.10 21.30
3×240+120 0.125 0.0754 0.151 0.0912 0.073 0.67 275 235 280 345 295 355 18.20 27.60
3×300+150 0.100 0.0601 0.122 0.0733 0.073 0.68 305 260 315 385 335 400 22.80 34.50
3×400+185 0.0778 0.0470 0.0961 0.0580 0.072 0.70 335 290 375 425 360 455 30.40 46.00
3×500+240 0.0605 0.0366 0.0759 0.0459 0.072 0.70 370 320 425 470 390 520 38.00 57.50
3×630+300 0.0469 0.0283 0.0610 0.0368 0.072 0.70 405 350 480 555 470 675 47.90 72.50

Cross-Sectional View

Cross-section of 1.1 kV three and half core PVC insulated armoured power cable

  1. Conductor: Aluminium / Copper as per Class 2 of IS 8130. Aluminium: 4, 6 and 10 sq. mm solid / stranded non-compacted circular; 16 sq. mm and above stranded compacted shaped. Copper: 4 and 6 sq. mm solid / stranded non-compacted circular; 10 sq. mm stranded compacted circular; 16 sq. mm and above stranded compacted shaped.
  2. Insulation: PVC Type-A / HR PVC Type-C as per IS 5831; colours: red, yellow, blue and black.
  3. Inner Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS.
  4. Armouring: Single layer of galvanized steel round wire / flat strip.
  5. Outer Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS. Colour: black or any other colour as per requirement.

TECHNICAL DETAILS – 1.1 kV FOUR CORE, ALUMINIUM / COPPER CONDUCTOR,
PVC INSULATED, ARMOURED CABLE

Physical Parameters

Four Core PVC armoured power cable – physical parameters (IS 1554 Part 1). Cable codes: AYFY / YFY, AYWY / YWY
Size Min. No. of Strands in Conductor Nominal Insulation Thickness Min. Inner Sheath Thickness Flat Strip Armoured (AYFY / YFY) Round Wire Armoured (AYWY / YWY)
Aluminium Copper Armour Strip Dimension Min. Outer Sheath Thickness Approx. Overall Dia Approx. Weight – Al Conductor Approx. Weight – Cu Conductor Nominal Dia of Armour Wire Min. Outer Sheath Thickness Approx. Overall Dia Approx. Weight – Al Conductor Approx. Weight – Cu Conductor
sq. mm N N mm mm mm mm mm kg/km kg/km mm mm mm kg/km kg/km
4 1/3 1/3 1.00 0.30 N/A N/A N/A N/A N/A 1.40 1.24 17 520 620
6 1/3 1/3 1.00 0.30 N/A N/A N/A N/A N/A 1.40 1.24 19 610 770
10 1/7 6 1.00 0.30 4×0.80 N/A 19 600 850 1.40 1.24 21 790 1060
16 6 6 1.00 0.30 4×0.80 1.40 21 750 1100 1.60 1.40 23 950 1350
25 6 6 1.20 0.30 4×0.80 1.40 24 950 1550 1.60 1.40 25 1200 1800
35 6 6 1.20 0.30 4×0.80 1.40 26 1150 2000 1.60 1.40 28 1450 2300
50 6 6 1.40 0.30 4×0.80 1.40 30 1450 2550 1.60 1.56 32 2000 3100
70 12 12 1.40 0.30 4×0.80 1.56 33 1850 3450 1.60 1.56 35 2400 4000
95 15 15 1.60 0.40 4×0.80 1.56 38 2350 4600 2.00 1.72 40 3000 5250
120 15 18 1.60 0.40 4×0.80 1.56 41 2800 5650 2.00 1.72 44 3500 6350
150 15 18 1.80 0.40 4×0.80 1.72 45 3300 6800 2.00 1.88 49 4500 7950
185 30 30 2.00 0.50 4×0.80 1.88 50 4000 8350 2.00 2.04 54 5350 9700
240 30 34 2.20 0.50 6.10×1.40 1.88 57 5100 10800 2.50 2.20 60 6500 12250
300 30 34 2.40 0.60 6.10×1.40 2.20 64 6200 13300 2.50 2.36 69 8500 15700
400 53 53 2.60 0.70 6.10×1.40 2.36 71 7650 16750 3.15 2.68 75 10200 19350
500 53 53 3.00 0.70 6.10×1.40 2.52 79 9600 21300 3.15 3.00 85 13550 25300
630 53 53 3.40 0.70 6.10×1.40 2.84 89 11700 27050 4.00 3.00 95 16350 31450

Electrical Parameters

Four Core PVC armoured power cable – electrical parameters
Size Max. Conductor DC Resistance at 20°C Approx. Conductor AC Resistance at 70°C Reactance at 50 Hz (Approx.) Capacitance (Approx.) Current Rating – Aluminium Conductor Current Rating – Copper Conductor Short Circuit Rating for 1 s
Aluminium Copper Aluminium Copper Ground Duct Air Ground Duct Air Aluminium Copper
sq. mm Ω/km Ω/km Ω/km Ω/km Ω/km µF/km A A A A A A kA kA
4 7.41 4.61 8.89 5.53 0.098 0.23 28 23 23 36 30 30 0.304 0.460
6 4.61 3.08 5.53 3.70 0.096 0.28 35 30 30 45 38 39 0.456 0.690
10 3.08 1.83 3.70 2.20 0.091 0.34 46 39 40 60 50 52 0.760 1.15
16 1.91 1.15 2.29 1.38 0.085 0.40 60 50 51 77 64 66 1.22 1.84
25 1.20 0.727 1.44 0.87 0.083 0.42 76 63 70 99 81 90 1.90 2.88
35 0.868 0.524 1.04 0.63 0.082 0.48 92 77 86 120 99 110 2.66 4.03
50 0.641 0.387 0.769 0.464 0.082 0.49 110 95 105 145 125 135 3.80 5.75
70 0.443 0.268 0.532 0.322 0.076 0.56 135 115 130 175 150 165 5.32 8.05
95 0.320 0.193 0.384 0.232 0.076 0.58 165 140 155 210 175 200 7.22 10.90
120 0.253 0.153 0.304 0.184 0.075 0.63 185 155 180 240 195 230 9.12 13.80
150 0.206 0.1240 0.247 0.1488 0.074 0.63 210 175 205 270 225 265 11.40 17.30
185 0.164 0.0991 0.197 0.1189 0.074 0.64 235 200 240 300 255 308 14.10 21.30
240 0.125 0.0754 0.151 0.0912 0.073 0.67 275 235 280 345 295 355 18.20 27.60
300 0.100 0.0601 0.122 0.0733 0.073 0.68 305 260 315 385 335 400 22.80 34.50
400 0.0778 0.0470 0.0961 0.0580 0.072 0.70 335 290 375 425 360 455 30.40 46.00
500 0.0605 0.0366 0.076 0.0459 0.072 0.70 370 320 425 470 390 520 38.00 57.50
630 0.0469 0.0283 0.0610 0.0368 0.072 0.70 405 350 480 555 470 675 47.90 72.50

Cross-Sectional View

Cross-section of 1.1 kV four core PVC insulated armoured power cable

  1. Conductor: Aluminium / Copper as per Class 2 of IS 8130. Aluminium: 4, 6 and 10 sq. mm solid / stranded non-compacted circular; 16 sq. mm and above stranded compacted shaped. Copper: 4 and 6 sq. mm solid / stranded non-compacted circular; 10 sq. mm stranded compacted circular; 16 sq. mm and above stranded compacted shaped.
  2. Insulation: PVC Type-A / HR PVC Type-C as per IS 5831; colours: red, yellow, blue and black.
  3. Inner Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS.
  4. Armouring: Single layer of galvanized steel round wire / flat strip.
  5. Outer Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS. Colour: black or any other colour as per requirement.

* Tabulated approximate weights are a guideline for transportation, loading and unloading only. Values marked “On request” are being confirmed with the manufacturer.
Normal current ratings are given for standard installation conditions. Where site conditions differ, apply the relevant rating factors (available on request).

FREQUENTLY ASKED QUESTIONS

What is the difference between AYFY and AYWY cable?

Both are aluminium conductor, PVC insulated, PVC sheathed armoured cables. AYFY has galvanized steel flat strip armour; AYWY has galvanized steel round wire armour, giving a slightly larger diameter and weight for the same size.

Why do single core armoured cables use aluminium armour?

In single core AC circuits, steel armour would carry induced currents and heat up. Non-magnetic aluminium armour (AYFaY / AYWaY) avoids this.

What is the current rating of a 4 core 95 sq. mm aluminium PVC armoured cable?

Under standard conditions the 4 core 95 sq. mm aluminium cable is rated 165 A in ground, 140 A in duct and 155 A in air. The copper version is rated 210 A, 175 A and 200 A respectively.

Which standard do these cables follow?

IS 1554 (Part 1) for PVC insulated heavy duty cables up to 1100 V, with conductors to IS 8130 Class 2 and PVC compounds to IS 5831.