AERIAL BUNCHED CABLE

1.1 kV aerial bunched cable (ABC) with XLPE insulated aluminium phase conductors and aluminium alloy messenger, with or without street light conductor. IS 14255 / IS 8130 / IS 398 (Part 4).

AERIAL BUNCHED CABLE (ABC) 1.1 kV
OVERHEAD POWER DISTRIBUTION CABLE, 1100 V

1.1 kV aerial bunched cable with three XLPE insulated phase conductors and aluminium alloy messenger

Aerial Bunched Cable (ABC) is recommended as an overhead distribution feeder in rural, residential and hill areas where underground installation is not possible. Insulated phase conductors are twisted around a messenger conductor, which reduces line faults, power theft and right-of-way clearance compared with bare conductors.

  • Voltage rating: 1100 V
  • Max. operating temperature: 90°C
  • Bending radius: 10 × overall diameter
  • Test voltage: 3000 V AC
  • Standards: IS 8130:2013, IS 398 (Part 4), IS 14255:1995
  • Configuration: Single or three phase, with or without street light conductor

CONSTRUCTION

Cross-section of aerial bunched cable showing phase, street light and messenger conductors

  1. Phase conductor: Stranded compacted aluminium conductor to IS 8130 Class 2, insulated with XLPE.
  2. Messenger conductor: Stranded circular or compacted heat-treated aluminium-magnesium alloy wire to IS 398 (Part 4); XLPE insulated if required.
  3. Street light conductor: Stranded aluminium conductor to IS 8130 Class 2, insulated with XLPE.
  4. Core identification: phase conductors one, two or three ridges; neutral four ridges; street light and messenger (if insulated) no mark.
  5. Compliance tests: conductor resistance (IS 8130); insulation resistance, elongation, water absorption and tensile tests (IS 14255:1995).

WEIGHT & DIMENSION DATA

Phase Conductor + Messenger (Bare)

ABC with bare messenger
Construction (N × mm²) Insulation Thickness Phase Conductor Overall Dia Messenger Overall Dia Weight (Approx.) Min. Breaking Load of Messenger
mm mm mm kg/km kN
1×16+1×25 1.20 7.53 6.45 139 7
3×16+1×25 1.20 7.53 6.45 278 7
1×25+1×25 1.20 8.85 6.45 170 7
3×25+1×25 1.20 8.85 6.45 371 7
1×35+1×25 1.20 10.00 6.45 202 7
3×35+1×25 1.20 10.00 6.45 466 7
1×50+1×35 1.50 12.05 7.60 286 9.8
3×50+1×35 1.50 12.05 7.60 667 9.8
1×70+1×50 1.50 13.73 9.05 391 14
3×70+1×50 1.50 13.73 9.05 899 14
1×95+1×70 1.50 15.52 10.77 526 19.7
3×95+1×70 1.50 15.52 10.77 1191 19.7

Phase Conductor + Messenger (Insulated)

ABC with insulated messenger
Construction (N × mm²) Insulation Thickness Phase Conductor Overall Dia Messenger Overall Dia Weight (Approx.) Min. Breaking Load of Messenger
Phase Messenger
mm mm mm mm kg/km kN
1×16+1×25 1.20 1.20 7.5 8.9 166 7
3×16+1×25 1.20 1.20 7.5 8.9 305 7
1×25+1×25 1.20 1.20 8.9 8.9 197 7
3×25+1×25 1.20 1.20 8.9 8.9 398 7
1×35+1×25 1.20 1.20 10.0 8.9 230 7
3×35+1×25 1.20 1.20 10.0 8.9 493 7
1×50+1×35 1.50 1.20 12.0 10.0 323 9.8
3×50+1×35 1.50 1.20 12.0 10.0 704 9.8
1×70+1×50 1.50 1.50 13.7 12.0 438 14
3×70+1×50 1.50 1.50 13.7 12.0 936 14
1×95+1×70 1.50 1.50 15.5 13.8 580 19.7
3×95+1×70 1.50 1.50 15.5 13.8 1246 19.7

Phase Conductor + Messenger (Bare) + Street Light

ABC with bare messenger and street light conductor
Construction (N × mm²) Insulation Thickness Phase Conductor Overall Dia Messenger Overall Dia Weight (Approx.) Min. Breaking Load of Messenger
Phase Messenger
mm mm mm mm kg/km kN
3×16+1×25+1×16 1.2 1.2 7.53 6.45 343 7.0
3×25+1×25+1×16 1.2 1.2 8.85 6.45 415 7.0
3×35+1×25+1×16 1.2 1.2 10.00 6.45 515 7.0
3×50+1×35+1×16 1.5 1.2 12.05 7.60 703 9.8
3×70+1×50+1×16 1.5 1.2 13.73 9.05 930 14.0
3×95+1×70+1×16 1.5 1.2 15.52 10.77 1215 19.7

Phase Conductor + Messenger (Insulated) + Street Light

ABC with insulated messenger and street light conductor
Construction (N × mm²) Insulation Thickness Phase Conductor Overall Dia Messenger Overall Dia Weight (Approx.) Min. Breaking Load of Messenger
Phase Messenger
mm mm mm mm kg/km kN
3×16+1×25+1×16 1.2 1.2 7.5 8.85 370 7.0
3×25+1×25+1×16 1.2 1.2 8.9 8.85 442 7.0
3×35+1×25+1×16 1.2 1.2 10.0 8.85 542 7.0
3×50+1×35+1×16 1.5 1.2 12.0 10.00 735 9.8
3×70+1×50+1×16 1.5 1.5 13.7 12.05 978 14.0
3×95+1×70+1×16 1.5 1.5 15.5 13.73 1270 19.7

ELECTRICAL CHARACTERISTICS

Current Carrying Capacity and Maximum DC Conductor Resistance

ABC electrical characteristics
Nominal Cross-Sectional Area Max. DC Conductor Resistance at 20°C Reactance Current Carrying Capacity in Air at 40°C
Phase Messenger
mm² Ω/km Ω/km Ω/km A
16 1.91 1.38 0.0834 72
25 1.20 1.38 0.0791 98
35 0.868 1.38 0.0765 119
50 0.641 0.986 0.0772 145
70 0.443 0.689 0.0748 185
95 0.32 0.492 0.0728 235

De-Rating Factor

De-rating factors for ambient air temperature
Air temperature 25°C 30°C 35°C 40°C 45°C 50°C 55°C 60°C
De-rating factor 1.14 1.1 1.05 1 0.95 0.89 0.84 0.77

FREQUENTLY ASKED QUESTIONS

What is aerial bunched cable used for?

ABC is used for overhead LT power distribution in rural, residential and hilly areas where underground cabling is not practical. Insulated conductors reduce faults, theft by hooking and clearance needed from trees and buildings.

What does 3×70+1×50+1×16 mean in ABC cable?

It means three 70 mm² phase conductors, one 50 mm² messenger conductor and one 16 mm² street light conductor.

What is the current rating of 70 mm² ABC cable?

A 70 mm² phase conductor carries 185 A in air at 40°C. At other air temperatures multiply by the de-rating factor, for example 0.95 at 45°C or 0.89 at 50°C.