POWER CABLE (XLPE INSULATED) COPPER / ALUMINIUM CONDUCTOR

Category:

1.1 kV XLPE insulated power cable with aluminium or copper conductor to IS 7098 (Part 1). Armoured and unarmoured, 1, 2, 3, 3.5 and 4 core, 4 sq. mm to 630 sq. mm.

POWER CABLE (XLPE INSULATED)
COPPER / ALUMINIUM CONDUCTOR

1.1 kV XLPE (cross-linked polyethylene) insulated power cables with aluminium or copper conductor, made to IS 7098 (Part 1). XLPE runs at up to 90°C, so it carries more current than a PVC cable of the same size and has a higher short circuit rating. Cable codes: A2XFY / 2XFY (strip armoured), A2XWY / 2XWY (wire armoured), A2XY / 2XY (unarmoured); 2X = XLPE insulation.

  • Voltage grade: 1.1 kV
  • Standard: IS 7098 (Part 1)
  • Conductor: Aluminium / Copper, Class 2 of IS 8130
  • Insulation: XLPE (90°C rated)
  • Sheath: PVC ST-1 (ST-2, FR, FRLS on request)
  • Types: Armoured and unarmoured
  • Cores: 1, 2, 3, 3½ and 4
  • Sizes: 4 sq. mm to 630 sq. mm

TECHNICAL DETAILS – 1.1 kV SINGLE CORE, ALUMINIUM / COPPER CONDUCTOR,
XLPE INSULATED, ARMOURED / UNARMOURED CABLE

Physical Parameters

Single Core XLPE power cable – physical parameters (IS 7098 Part 1)
Size Insulation Thickness (Nom.) Armour Dimension (Nom.) Outer Sheath Thickness Approx. Overall Diameter Approx. Weight – Round Wire Armoured Approx. Weight – Flat Strip Armoured Approx. Weight – Unarmoured
Armoured Unarmoured Round Wire Strip Round Wire Arm. (Min.) Flat Strip Arm. (Min.) Unarmoured (Nom.) Round Wire Arm. Flat Strip Arm. Unarmoured Aluminium Copper Aluminium Copper Aluminium Copper
sq. mm mm mm mm mm mm mm mm mm mm mm kg/km kg/km kg/km kg/km kg/km kg/km
4 – 0.7 – – – – 1.8 – – 8.5 – – – – 80 100
6 – 0.7 – – – – 1.8 – – 9.0 – – – – 95 120
10 1.0 0.7 1.4 – 1.24 – 1.8 12.0 – 9.5 165 225 – – 110 165
16 1.0 0.7 1.4 – 1.24 – 1.8 13.0 – 10.5 200 290 – – 135 225
25 1.2 0.9 1.4 – 1.24 – 1.8 14.5 – 12.0 250 400 – – 175 325
35 1.2 0.9 1.4 – 1.24 – 1.8 15.5 – 13.0 300 500 – – 215 415
50 1.3 1.0 1.4 – 1.24 – 1.8 16.5 – 14.0 350 630 – – 260 540
70 1.4 1.1 1.6 – 1.24 – 1.8 18.5 – 16.0 445 840 – – 340 740
95 1.4 1.1 1.6 4×0.8 1.4 1.4 1.8 20.5 19.5 17.5 580 1130 515 1070 425 980
120 1.5 1.2 1.6 4×0.8 1.4 1.4 1.8 22.5 21.0 19.0 675 1375 610 1310 510 1210
150 1.7 1.4 1.6 4×0.8 1.4 1.4 2.0 24.0 23.0 21.5 On request 1670 715 1595 630 1510
185 1.9 1.6 1.6 4×0.8 1.4 1.4 2.0 26.0 25.0 23.5 945 2035 865 1960 765 1860
240 2.0 1.7 1.6 4×0.8 1.4 1.4 2.0 28.5 27.5 26.0 1150 2600 1060 2510 955 2405
300 2.1 1.8 1.6 4×0.8 1.56 1.56 2.0 31.0 30.0 28.0 1390 3210 1290 3120 1145 2970
400 2.4 2.0 2.0 4×0.8 1.56 1.56 2.2 35.5 33.5 32.0 1790 4115 1605 3925 1460 3785
500 2.6 2.2 2.0 4×0.8 1.56 1.56 2.2 39.6 37.5 36.0 2210 5185 1990 4970 1830 4810
630 2.8 2.4 2.0 4×0.8 1.72 1.72 2.2 43.5 41.5 39.5 2745 6585 2500 6360 2300 6150

Electrical Parameters

Single Core XLPE power cable – electrical parameters
Size Max. DC Resistance at 20°C Approx. AC Resistance at 90°C Approx. Reactance at 50 Hz Current Rating – Direct in Ground at 30°C Current Rating – In Duct at 30°C Current Rating – In Air at 40°C Short Circuit Rating for 1 s
Aluminium Copper Aluminium Copper Armoured Unarmoured Aluminium Copper Aluminium Copper Aluminium Copper Aluminium Copper
sq. mm Ω/km Ω/km Ω/km Ω/km Ω/km Ω/km A A A A A A kA kA
4 7.41 4.61 9.48 5.90 – 0.132 37 47 34 43 33 41 0.38 0.57
6 4.61 3.08 5.90 3.94 – 0.123 47 58 43 53 43 52 0.56 0.86
10 3.08 1.83 3.94 2.34 0.134 0.114 59 77 54 70 55 71 0.94 1.43
16 1.91 1.15 2.44 1.47 0.125 0.108 76 98 69 89 72 94 1.50 2.29
25 1.20 0.727 1.54 0.930 0.117 0.102 98 126 89 114 98 126 2.36 3.56
35 0.868 0.524 1.11 0.671 0.112 0.098 116 150 106 136 119 154 3.30 5.00
50 0.641 0.387 0.82 0.495 0.106 0.093 137 On request 124 160 145 187 4.72 7.15
70 0.443 0.268 0.567 0.343 0.10 0.089 168 216 151 195 185 238 6.60 10.01
95 0.320 0.193 0.41 0.247 0.099 0.086 202 260 181 233 235 303 8.96 13.58
120 0.253 0.153 0.324 0.196 0.095 0.083 230 295 206 264 276 354 11.32 17.16
150 0.206 0.124 0.264 0.156 0.093 0.082 256 329 229 294 314 403 14.16 21.45
185 0.164 0.0991 0.210 0.127 0.092 0.082 290 371 258 330 366 468 17.46 26.45
240 0.125 0.0754 0.160 0.0965 0.089 0.08 335 427 298 379 434 553 22.65 34.32
300 0.100 0.0601 0.128 0.0769 0.087 0.079 376 477 333 422 500 634 28.32 42.90
400 0.0778 0.047 0.100 0.0604 0.086 0.078 429 537 378 473 589 737 37.76 57.25
500 0.0605 0.0366 0.0774 0.0468 0.084 0.077 485 598 426 525 685 844 47.20 71.50
630 0.0469 0.0283 0.0600 0.0362 0.083 0.076 546 661 477 578 793 961 59.45 90.10

Cross-Sectional View

Cross-section of 1.1 kV single core XLPE insulated armoured power cable

  1. Conductor: Aluminium / Copper as per Class 2 of IS 8130. Aluminium: 4, 6 and 10 sq. mm solid / stranded non-compacted circular; 16 sq. mm and above stranded compacted circular. Copper: 4 and 6 sq. mm solid / stranded non-compacted circular; 10 sq. mm and above stranded compacted circular.
  2. Insulation: XLPE; colour: black.
  3. Inner Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS.
  4. Armouring: Single layer of aluminium round wire / flat strip.
  5. Outer Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS. Colour: black or any other colour as per requirement.

TECHNICAL DETAILS – 1.1 kV TWO CORE, ALUMINIUM / COPPER CONDUCTOR,
XLPE INSULATED, ARMOURED / UNARMOURED CABLE

Physical Parameters

Two Core XLPE power cable – physical parameters (IS 7098 Part 1)
Size Insulation Thickness (Nom.) Inner Sheath Thickness Armour Dimension (Nom.) Outer Sheath Thickness Approx. Overall Diameter Approx. Weight – Round Wire Armoured Approx. Weight – Flat Strip Armoured Approx. Weight – Unarmoured
Round Wire Strip Round Wire Arm. (Min.) Flat Strip Arm. (Min.) Unarmoured (Nom.) Round Wire Arm. Flat Strip Arm. Unarmoured Aluminium Copper Aluminium Copper Aluminium Copper
sq. mm mm mm mm mm mm mm mm mm mm mm kg/km kg/km kg/km kg/km kg/km kg/km
4 0.7 0.3 1.4 – 1.24 – 1.8 16.5 – 14.0 470 490 – – 235 265
6 0.7 0.3 1.4 – 1.24 – 1.8 17.5 – 14.5 560 575 – – 290 325
10 0.7 0.3 1.4 – 1.24 – 1.8 18.5 – 16.5 580 700 – – 285 410
16 0.7 0.3 1.4 – 1.4 – 1.8 20.5 – 18.0 700 885 – – 360 545
25 0.9 0.3 1.6 4×0.8 1.4 1.4 2.0 22.5 21.0 19.5 850 1150 660 960 420 740
35 0.9 0.3 1.6 4×0.8 1.4 1.4 2.0 23.5 22.0 21.0 955 1370 755 1175 510 940
50 1.0 0.3 1.6 4×0.8 1.4 1.4 2.0 25.5 24.5 23.5 1135 1700 895 1460 640 1210
70 1.1 0.3 1.6 4×0.8 1.56 1.56 2.0 28.5 27.5 26.0 1390 2210 1125 1950 810 1630
95 1.1 0.4 1.6 4×0.8 1.56 1.56 2.2 31.0 29.5 28.5 1800 2950 1320 2470 1010 2160
120 1.2 0.4 2.0 4×0.8 1.56 1.56 2.2 34.0 32.0 31.0 2070 3510 1560 3005 1210 2655
150 1.4 0.4 2.0 4×0.8 1.72 1.72 2.2 37.0 35.0 34.0 2415 4210 1850 3650 1440 3255
185 1.6 0.5 2.0 4×0.8 1.88 1.72 2.4 40.5 38.0 37.5 2850 5090 2190 4435 1770 4020
240 1.7 0.5 2.5 6.10×1.40 2.04 1.88 2.6 45.5 42.0 41.0 3710 6665 2660 5620 2210 5165
300 1.8 0.6 2.5 6.10×1.40 2.2 2.04 2.8 49.0 46.0 45.0 4345 8055 3200 6910 2700 6415
400 2.0 0.6 2.5 6.10×1.40 2.36 2.36 3.0 54.5 51.5 50.5 5195 9930 3955 8690 3375 8110

Electrical Parameters

Two Core XLPE power cable – electrical parameters
Size Max. DC Resistance at 20°C Approx. AC Resistance at 90°C Approx. Reactance at 50 Hz Current Rating – Direct in Ground at 30°C Current Rating – In Duct at 30°C Current Rating – In Air at 40°C Short Circuit Rating for 1 s
Aluminium Copper Aluminium Copper Armoured Unarmoured Aluminium Copper Aluminium Copper Aluminium Copper Aluminium Copper
sq. mm Ω/km Ω/km Ω/km Ω/km Ω/km Ω/km A A A A A A kA kA
4 7.41 4.61 9.48 5.90 0.0927 0.0927 42 54 36 43 38 48 0.38 0.57
6 4.61 3.08 5.90 3.94 0.0884 0.0884 55 67 46 53 50 61 0.56 0.86
10 3.08 1.83 3.94 2.34 0.0837 0.0837 68 89 57 70 64 83 0.94 1.43
16 1.91 1.15 2.44 1.47 0.0808 0.0808 89 115 74 89 83 108 1.50 2.29
25 1.20 0.727 1.54 0.930 0.0802 0.0802 114 147 95 114 109 140 2.36 3.56
35 0.868 0.524 1.11 0.671 0.080 0.080 136 176 113 136 133 172 3.30 5.00
50 0.641 0.387 0.82 0.495 0.076 0.076 161 208 134 160 162 208 4.72 7.15
70 0.443 0.268 0.567 0.343 0.075 0.075 197 253 164 195 204 262 6.60 10.01
95 0.320 0.193 0.41 0.247 0.073 0.073 235 302 196 233 251 322 8.96 13.58
120 0.253 0.153 0.324 0.196 0.071 0.071 266 340 222 264 287 368 11.32 17.16
150 0.206 0.124 0.264 0.156 0.071 0.071 296 379 248 294 328 419 14.16 21.45
185 0.164 0.0991 0.210 0.127 0.071 0.071 335 425 281 330 379 482 17.46 26.45
240 0.125 0.0754 0.160 0.0965 0.071 0.071 385 486 324 379 448 566 22.65 34.32
300 0.100 0.0601 0.128 0.0769 0.071 0.071 432 541 364 422 513 644 28.32 42.90
400 0.0778 0.047 0.100 0.0604 0.070 0.070 487 602 412 473 593 734 37.76 57.25

Cross-Sectional View

Cross-section of 1.1 kV two core XLPE insulated armoured power cable

  1. Conductor: Aluminium / Copper as per Class 2 of IS 8130. Aluminium: 4, 6 and 10 sq. mm solid / stranded non-compacted circular; 16 sq. mm and above stranded compacted shaped. Copper: 4 and 6 sq. mm solid / stranded non-compacted circular; 10 sq. mm stranded compacted circular; 16 sq. mm and above stranded compacted shaped.
  2. Insulation: XLPE; colours: red and black.
  3. Inner Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS.
  4. Outer Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS. Colour: black or any other colour as per requirement.

Armouring: Single layer of galvanized steel round wire / flat strip.

TECHNICAL DETAILS – 1.1 kV THREE CORE, ALUMINIUM / COPPER CONDUCTOR,
XLPE INSULATED, ARMOURED / UNARMOURED CABLE

Physical Parameters

Three Core XLPE power cable – physical parameters (IS 7098 Part 1)
Size Insulation Thickness (Nom.) Inner Sheath Thickness Armour Dimension (Nom.) Outer Sheath Thickness Approx. Overall Diameter Approx. Weight – Round Wire Armoured Approx. Weight – Flat Strip Armoured Approx. Weight – Unarmoured
Round Wire Strip Round Wire Arm. (Min.) Flat Strip Arm. (Min.) Unarmoured (Nom.) Round Wire Arm. Flat Strip Arm. Unarmoured Aluminium Copper Aluminium Copper Aluminium Copper
sq. mm mm mm mm mm mm mm mm mm mm mm kg/km kg/km kg/km kg/km kg/km kg/km
4 0.7 0.3 1.4 – 1.24 – 1.8 16.5 – 14.5 505 540 – – 260 310
6 0.7 0.3 1.4 – 1.24 – 1.8 18.0 – 16.0 600 645 – – 320 385
10 0.7 0.3 1.4 – 1.24 – 1.8 19.0 – 17.5 625 810 – – 325 505
16 0.7 0.3 1.6 4×0.8 1.4 1.24 1.8 19.0 17.5 16.5 700 980 555 810 345 625
25 0.9 0.3 1.6 4×0.8 1.4 1.4 2.0 22.0 21.0 20.0 905 1360 715 1170 505 955
35 0.9 0.3 1.6 4×0.8 1.4 1.4 2.0 24.0 22.5 22.0 1060 1690 845 1470 615 1245
50 1.0 0.3 1.6 4×0.8 1.56 1.4 2.0 27.0 25.5 24.5 1320 2170 1045 1890 775 1625
70 1.1 0.4 2.0 4×0.8 1.56 1.56 2.2 31.0 29.0 28.0 1800 3030 1340 2580 1040 2270
95 1.1 0.4 2.0 4×0.8 1.56 1.56 2.2 34.0 32.0 31.0 2150 3875 1640 3365 1295 3020
120 1.2 0.4 2.0 4×0.8 1.72 1.56 2.2 37.5 35.0 34.0 2545 4710 1955 4120 1570 3740
150 1.4 0.5 2.0 4×0.8 1.88 1.72 2.4 41.0 38.5 38.0 3015 5710 2330 5025 1920 4620
185 1.6 0.5 2.5 4×0.8 2.04 1.88 2.6 46.0 42.5 42.0 3905 7275 2840 6210 2375 5745
240 1.7 0.6 2.5 6.10×1.40 2.2 2.04 2.8 50.5 47.5 47.0 4725 9160 3525 7960 3020 7450
300 1.8 0.6 2.5 6.10×1.40 2.36 2.2 3.0 55.5 52.0 51.5 5530 11095 4230 9800 3680 9250
400 2.0 0.6 3.15 6.10×1.40 On request 2.52 3.2 63.5 59.0 58.0 7445 14550 5320 12425 4670 11780

Electrical Parameters

Three Core XLPE power cable – electrical parameters
Size Max. DC Resistance at 20°C Approx. AC Resistance at 90°C Approx. Reactance at 50 Hz Current Rating – Direct in Ground at 30°C Current Rating – In Duct at 30°C Current Rating – In Air at 40°C Short Circuit Rating for 1 s
Aluminium Copper Aluminium Copper Armoured Unarmoured Aluminium Copper Aluminium Copper Aluminium Copper Aluminium Copper
sq. mm Ω/km Ω/km Ω/km Ω/km Ω/km Ω/km A A A A A A kA kA
4 7.41 4.61 9.48 5.90 0.0927 0.0927 35 45 30 38 32 41 0.38 0.57
6 4.61 3.08 5.90 3.94 0.0884 0.0884 46 56 38 47 42 52 0.56 0.86
10 3.08 1.83 3.94 2.34 0.0837 0.0837 57 74 48 62 54 70 0.94 1.43
16 1.91 1.15 2.44 1.47 0.0802 0.0808 74 95 61 79 69 89 1.50 2.29
25 1.20 0.727 1.54 0.930 0.080 0.0802 95 112 79 102 93 119 2.36 3.56
35 0.868 0.524 1.11 0.671 0.079 0.080 114 146 94 122 114 147 3.30 5.00
50 0.641 0.387 0.82 0.495 0.078 0.076 134 173 112 144 138 179 4.72 7.15
70 0.443 0.268 0.567 0.343 0.077 0.075 164 212 137 177 175 226 6.60 10.01
95 0.320 0.193 0.41 0.247 0.077 0.073 197 254 164 212 216 279 8.96 13.58
120 0.253 0.153 0.324 0.196 0.072 0.071 223 287 187 240 249 320 11.32 17.16
150 0.206 0.124 0.264 0.156 0.072 0.071 249 321 209 269 284 365 14.16 21.45
185 0.164 0.0991 0.210 0.127 0.072 0.071 282 362 238 304 329 422 17.46 26.45
240 0.125 0.0754 0.160 0.0965 0.072 0.071 327 418 276 352 392 500 22.65 34.32
300 0.100 0.0601 0.128 0.0769 0.071 0.071 369 469 312 396 452 574 28.32 42.90
400 0.0778 0.047 0.100 0.0604 0.070 0.070 420 528 356 447 526 662 37.76 57.25

Cross-Sectional View

Cross-section of 1.1 kV three core XLPE insulated armoured power cable

  1. Conductor: Aluminium / Copper as per Class 2 of IS 8130. Aluminium: 4, 6 and 10 sq. mm solid / stranded non-compacted circular; 16 sq. mm and above stranded compacted shaped. Copper: 4 and 6 sq. mm solid / stranded non-compacted circular; 10 sq. mm stranded compacted circular; 16 sq. mm and above stranded compacted shaped.
  2. Insulation: XLPE; colours: red, yellow and blue.
  3. Inner Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS.
  4. Armouring: Single layer of galvanized steel round wire / flat strip.
  5. Outer Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS. Colour: black or any other colour as per requirement.

TECHNICAL DETAILS – 1.1 kV THREE & HALF CORE, ALUMINIUM / COPPER CONDUCTOR,
XLPE INSULATED, ARMOURED / UNARMOURED CABLE

Physical Parameters

Three & Half Core XLPE power cable – physical parameters (IS 7098 Part 1)
Size (Phase / Neutral) Insulation Thickness (Nom.) Inner Sheath Thickness Armour Dimension (Nom.) Outer Sheath Thickness Approx. Overall Diameter Approx. Weight – Round Wire Armoured Approx. Weight – Flat Strip Armoured Approx. Weight – Unarmoured
Round Wire Strip Round Wire Arm. (Min.) Flat Strip Arm. (Min.) Unarmoured (Nom.) Round Wire Arm. Flat Strip Arm. Unarmoured Aluminium Copper Aluminium Copper Aluminium Copper
sq. mm mm mm mm mm mm mm mm mm mm mm kg/km kg/km kg/km kg/km kg/km kg/km
25/16 0.9/0.7 0.3 1.6 4×0.8 1.4 1.4 2.0 24.0 23.0 22.0 1030 1575 815 1360 585 1130
35/16 0.9/0.7 0.3 1.6 4×0.8 1.4 1.4 2.0 26.0 25.0 24.0 1205 1925 970 1690 700 1420
50/25 1.0/0.9 0.3 1.6 4×0.8 1.56 1.4 2.0 29.5 28.0 27.0 1500 2505 1210 2210 900 1900
70/35 1.1/0.9 0.4 2.0 4×0.8 1.56 1.56 2.2 34.0 32.0 31.0 2050 3495 1540 2985 1200 2640
95/50 1.1/1.0 0.4 2.0 4×0.8 1.56 1.56 2.2 37.5 35.0 34.5 2470 4480 1880 3890 1500 3515
120/70 1.2/1.1 0.4 2.0 4×0.8 1.72 1.56 2.2 41.0 39.0 37.5 2935 5515 2290 4870 1850 4425
150/70 1.4/1.1 0.5 2.0 4×0.8 1.88 1.72 2.4 45.0 43.0 42.0 3425 6530 2680 5785 2220 5325
185/95 1.6/1.1 0.5 2.5 4×0.8 2.04 1.88 2.6 50.5 47.0 46.6 4455 8400 3265 7210 2745 6690
240/120 1.7/1.2 0.6 2.5 6.10×1.40 2.2 2.04 2.8 56.0 52.5 52.0 5380 10535 4045 9200 3500 8650
300/150 1.8/1.4 0.6 2.5 6.10×1.40 2.36 2.2 3.0 61.0 57.5 57.0 6320 12780 4850 11315 4260 10725
400/185 2.0/1.6 0.7 3.15 6.10×1.40 2.68 2.52 3.4 70.5 65.5 65.5 8460 16690 6115 14340 5470 13700

Electrical Parameters

Three & Half Core XLPE power cable – electrical parameters
Size (Phase / Neutral) Max. DC Resistance at 20°C Approx. AC Resistance at 90°C Approx. Reactance at 50 Hz Current Rating – Direct in Ground at 30°C Current Rating – In Duct at 30°C Current Rating – In Air at 40°C Short Circuit Rating for 1 s
Aluminium Copper Aluminium Copper Armoured Unarmoured Aluminium Copper Aluminium Copper Aluminium Copper Aluminium Copper
sq. mm Ω/km Ω/km Ω/km Ω/km Ω/km Ω/km A A A A A A kA kA
25/16 1.20 0.727 1.54 0.930 0.080 0.080 95 122 79 102 93 119 2.36 3.56
35/16 0.868 0.524 1.11 0.671 0.079 0.079 114 146 94 122 114 147 3.30 5.00
50/25 0.641 0.387 0.82 0.495 0.078 0.078 134 173 112 144 138 179 4.72 7.15
70/35 0.443 0.268 0.567 0.343 0.077 0.077 164 212 137 177 175 226 6.60 10.01
95/50 0.320 0.193 0.41 0.247 0.077 0.077 197 254 164 212 216 279 8.96 13.58
120/70 0.253 0.153 0.324 0.196 0.072 0.072 223 287 187 240 249 320 11.32 17.16
150/70 0.206 0.124 0.264 0.156 0.072 0.072 249 321 209 269 284 365 14.16 21.45
185/95 0.164 0.0991 0.210 0.127 0.072 0.072 282 362 238 304 329 422 17.46 26.45
240/120 0.125 0.0754 0.160 0.0965 0.072 0.072 327 418 276 352 392 500 22.65 34.32
300/150 0.100 0.0601 0.128 0.0769 0.071 0.071 369 469 312 396 452 574 28.32 42.90
400/185 0.0778 0.047 0.100 0.0604 0.070 0.070 420 528 356 447 526 662 37.76 57.25

Cross-Sectional View

Cross-section of 1.1 kV three and half core XLPE insulated armoured power cable

  1. Conductor: Aluminium / Copper as per Class 2 of IS 8130. Aluminium: 4, 6 and 10 sq. mm solid / stranded non-compacted circular; 16 sq. mm and above stranded compacted shaped. Copper: 4 and 6 sq. mm solid / stranded non-compacted circular; 10 sq. mm stranded compacted circular; 16 sq. mm and above stranded compacted shaped.
  2. Insulation: XLPE; colours: red, yellow, blue and black.
  3. Inner Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS.
  4. Armouring: Single layer of galvanized steel round wire / flat strip.
  5. Outer Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS. Colour: black or any other colour as per requirement.

TECHNICAL DETAILS – 1.1 kV FOUR CORE, ALUMINIUM / COPPER CONDUCTOR,
XLPE INSULATED, ARMOURED / UNARMOURED CABLE

Physical Parameters

Four Core XLPE power cable – physical parameters (IS 7098 Part 1)
Size Insulation Thickness (Nom.) Inner Sheath Thickness Armour Dimension (Nom.) Outer Sheath Thickness Approx. Overall Diameter Approx. Weight – Round Wire Armoured Approx. Weight – Flat Strip Armoured Approx. Weight – Unarmoured
Round Wire Strip Round Wire Arm. (Min.) Flat Strip Arm. (Min.) Unarmoured (Nom.) Round Wire Arm. Flat Strip Arm. Unarmoured Aluminium Copper Aluminium Copper Aluminium Copper
sq. mm mm mm mm mm mm mm mm mm mm mm kg/km kg/km kg/km kg/km kg/km kg/km
4 0.7 0.3 1.4 – 1.24 – 1.8 17.0 – 16.0 565 625 – – 300 365
6 0.7 0.3 1.4 – 1.24 – 1.8 18.5 – 17.5 690 760 – – 375 465
10 0.7 0.3 1.4 – 1.4 – 1.8 21.0 – 19.0 730 974 – – 385 625
16 0.7 0.3 1.6 4×0.8 1.4 1.4 1.8 21.5 20.0 21.0 830 1210 670 1050 490 860
25 0.9 0.3 1.6 4×0.8 1.4 1.4 2.0 25.5 24.0 23.0 1110 1710 885 1490 640 1240
35 0.9 0.3 1.6 4×0.8 1.4 1.4 2.0 27.5 26.5 25.5 1315 2150 1070 1905 785 1615
50 1.0 0.3 1.6 4×0.8 1.56 1.56 2.0 31.5 30.0 29.0 1640 2770 1345 2475 1000 2120
70 1.1 0.4 2.0 4×0.8 1.56 1.56 2.2 36.0 34.0 33.0 2250 3900 1715 3360 1335 2975
95 1.1 0.4 2.0 4×0.8 1.72 1.56 2.2 40.0 38.0 37.0 2735 5040 2090 4390 1675 3970
120 1.2 0.4 2.0 4×0.8 1.88 1.72 2.4 44.0 41.5 40.5 3260 6150 2515 5405 2075 4955
150 1.4 0.5 2.0 4×0.8 2.04 1.88 2.6 49.5 46.5 45.5 4215 7810 3040 6630 2545 6130
185 1.6 0.5 2.5 4×0.8 2.2 2.04 2.8 54.0 51.0 50.0 4945 9435 3670 8160 3135 7615
240 1.7 0.6 2.5 6.10×1.40 2.36 2.2 3.0 60.0 57.0 56.5 6050 On request 4580 10470 3990 9890
300 1.8 0.6 2.5 6.10×1.40 2.52 2.36 3.2 67.5 62.5 62.0 7790 On request 5525 12950 4905 12310
400 2.0 0.6 3.15 6.10×1.40 2.84 2.68 3.6 75.5 71.0 71.0 9520 On request 6945 16415 6245 15700

Electrical Parameters

Four Core XLPE power cable – electrical parameters
Size Max. DC Resistance at 20°C Approx. AC Resistance at 90°C Approx. Reactance at 50 Hz Current Rating – Direct in Ground at 30°C Current Rating – In Duct at 30°C Current Rating – In Air at 40°C Short Circuit Rating for 1 s
Aluminium Copper Aluminium Copper Armoured Unarmoured Aluminium Copper Aluminium Copper Aluminium Copper Aluminium Copper
sq. mm Ω/km Ω/km Ω/km Ω/km Ω/km Ω/km A A A A A A kA kA
4 7.41 4.61 9.48 5.90 0.0927 0.0927 35 45 30 38 32 41 0.38 0.57
6 4.61 3.08 5.90 3.94 0.0884 0.0884 46 56 38 47 42 52 0.56 0.86
10 3.08 1.83 3.94 2.34 0.0837 0.0837 57 74 48 62 54 70 0.94 1.43
16 1.91 1.15 2.44 1.47 0.0802 0.0808 74 95 61 79 69 89 1.50 2.29
25 1.20 0.727 1.54 0.930 0.080 0.0802 95 112 79 102 93 119 2.36 3.56
35 0.868 0.524 1.11 0.671 0.079 0.080 114 146 94 122 114 147 3.30 5.00
50 0.641 0.387 0.82 0.495 0.078 0.076 134 173 112 144 138 179 4.72 7.15
70 0.443 0.268 0.567 0.343 0.077 0.075 164 212 137 177 175 226 6.60 10.01
95 0.320 0.193 0.41 0.247 0.077 0.073 197 254 164 212 216 279 8.96 13.58
120 0.253 0.153 0.324 0.196 0.072 0.071 223 287 187 240 249 320 11.32 17.16
150 0.206 0.124 0.264 0.156 0.072 0.071 249 321 209 269 284 365 14.16 21.45
185 0.164 0.0991 0.210 0.127 0.072 0.071 282 362 238 304 329 422 17.46 26.45
240 0.125 0.0754 0.160 0.0965 0.072 0.071 327 418 276 352 392 500 22.65 34.32
300 0.100 0.0601 0.128 0.0769 0.071 0.071 369 469 312 396 452 574 28.32 42.90
400 0.0778 0.047 0.100 0.0604 0.070 0.070 420 528 356 447 526 662 37.76 57.25

Cross-Sectional View

Cross-section of 1.1 kV four core XLPE insulated armoured power cable

  1. Conductor: Aluminium / Copper as per Class 2 of IS 8130. Aluminium: 4, 6 and 10 sq. mm solid / stranded non-compacted circular; 16 sq. mm and above stranded compacted shaped. Copper: 4 and 6 sq. mm solid / stranded non-compacted circular; 10 sq. mm stranded compacted circular; 16 sq. mm and above stranded compacted shaped.
  2. Insulation: XLPE; colours: red, yellow, blue and black.
  3. Inner Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS.
  4. Armouring: Single layer of galvanized steel round wire / flat strip.
  5. Outer Sheath: PVC Type ST-1 as per IS 5831; options: PVC Type ST-2 / FR / FRLS. Colour: black or any other colour as per requirement.

* Tabulated approximate weights are a guideline for transportation, loading and unloading only. Values marked “On request” are being confirmed with the manufacturer.
Normal current ratings are given for standard installation conditions. Where site conditions differ, apply the relevant rating factors (available on request).

FREQUENTLY ASKED QUESTIONS

What is the difference between XLPE and PVC insulated cable?

XLPE insulation is rated for 90°C continuous operation against 70°C for PVC, so an XLPE cable carries more current and withstands higher short circuit current for the same conductor size. It is also lighter and has better moisture resistance.

What is the current rating of a 4 core 95 sq. mm aluminium XLPE armoured cable?

Under standard conditions it is rated 197 A direct in ground, 164 A in duct and 216 A in air. The copper version is rated 254 A, 212 A and 279 A respectively.

What does A2XFY mean?

A2XFY is an aluminium conductor (A), XLPE insulated (2X), galvanized steel flat strip armoured (F), PVC outer sheathed (Y) cable. 2XFY is the copper conductor version.

Which standard applies to LT XLPE cables?

IS 7098 (Part 1) covers XLPE insulated PVC sheathed cables for working voltages up to and including 1100 V.