ALL ALUMINIUM CONDUCTOR STEEL REINFORCED (ACSR)

ACSR conductors are concentrically stranded, with one or more layers of hard drawn aluminium wire on a galvanized steel wire core. The core can be a single wire or stranded, depending on the conductor size. ACSR is used for overhead transmission and distribution lines.
- Standard: IS 398 (Part 2)
- Construction: Hard drawn aluminium wires over galvanized steel core
- Steel coating: Zinc, Class A / Class B
- Sizes: 10 mm² to 560 mm² nominal area
- Finish: Standard, non-specular (dull) or colour coated on request
FEATURES
- High tensile strength
- Better sag properties
- Economic design
- Suitable for remote applications involving long spans
ACSR – IS 398 (PART 2) PHYSICAL PARAMETERS
| Nominal Area | Sectional Area | No. of Wires | Wire Diameter | Diameter of Complete Conductor | Weight | Rated Strength | DC Resistance at 20°C | Current Capacity | |||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Aluminium | Steel | Aluminium | Steel | at 75°C | at 85°C | ||||||
| mm² | mm² | No. | No. | mm | mm | mm | kg/km | kN | Ω/km | A | A |
| 10 | 12.40 | 6 | 1 | 1.50 | 1.50 | 4.50 | 43 | 4.09 | 2.7064 | 59 | 69 |
| 18 | 21.1 | 6 | 1 | 1.96 | 1.96 | 5.88 | 73 | 6.86 | 1.5851 | 81 | 97 |
| 20 | 24.5 | 6 | 1 | 2.11 | 2.11 | 6.33 | 85 | 7.61 | 1.3675 | 89 | 106 |
| 30 | 36.9 | 6 | 1 | 2.59 | 2.59 | 7.77 | 128 | 11.17 | 0.9076 | 114 | 136 |
| 50 | 61.7 | 6 | 1 | 3.35 | 3.35 | 10.05 | 214 | 18.37 | 0.5426 | 155 | 186 |
| 80 | 92.0 | 6 | 1 | 4.09 | 4.09 | 12.27 | 319 | 27.02 | 0.3639 | 196 | 237 |
| 100 | 118.5 | 6 | 7 | 4.72 | 1.57 | 14.15 | 394 | 32.53 | 0.2733 | 231 | 282 |
| 130 | 151.8 | 26 | 7 | 2.54 | 1.91 | 15.89 | 521 | 45.65 | 0.2192 | 285 | 350 |
| 150 | 194.9 | 30 | 7 | 2.59 | 2.59 | 18.13 | 726 | 67.63 | 0.1828 | 315 | 389 |
| 180 | 226.2 | 30 | 7 | 2.79 | 2.79 | 19.53 | 842 | 78.35 | 0.1576 | 365 | 450 |
| 200 | 261.5 | 30 | 7 | 3.00 | 3.00 | 21.00 | 974 | 90.56 | 0.1363 | 374 | 465 |
| 400 | 425.2 | 42 | 7 | 3.50 | 1.96 | 26.88 | 1286 | 90.43 | 0.0717 | 525 | 664 |
| 420 | 484.5 | 54 | 7 | 3.18 | 3.18 | 28.62 | 1627 | 131.44 | 0.0677 | 546 | 693 |
| 520 | 552.0 | 42 | 7 | 3.99 | 2.21 | 30.57 | 1666 | 112.31 | 0.0552 | 612 | 783 |
| 530 | 597.0 | 54 | 7 | 3.53 | 3.53 | 31.77 | 2004 | 159.60 | 0.0549 | 620 | 790 |
| 560 | 591.7 | 42 | 7 | 4.13 | 2.30 | 31.68 | 1787 | 120.57 | 0.0515 | 631 | 808 |
Current capacity is based on the referenced conductor temperature, 0.56 m/s wind, 0 m elevation, 0.45 emissivity, 0.80 absorptivity, 45°C ambient temperature and 1045 W/m² solar radiation. Custom conductor sizes can be designed to customer requirements.
FREQUENTLY ASKED QUESTIONS
What is an ACSR conductor?
ACSR (Aluminium Conductor Steel Reinforced) is a bare overhead conductor made of aluminium wires stranded over a galvanized steel core. The aluminium carries the current and the steel core provides tensile strength for long spans.
What is the current capacity of a 100 mm² ACSR conductor?
A 100 mm² nominal ACSR conductor (6 aluminium + 7 steel wires, 14.15 mm diameter) carries about 231 A at 75°C and 282 A at 85°C under the stated reference conditions.
Which standard covers ACSR conductors in India?
IS 398 (Part 2) covers aluminium conductors, galvanized steel reinforced, for overhead power lines.




Reviews
There are no reviews yet.